Malaysia

Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

RE22R1ACMR Product picture Schneider Electric

View all Zelio Time Relays

Zelio Time Relays - RE22R1ACMR

Relay Output

RE22R1ACMR Product picture Schneider Electric
View all Zelio Time Relays
Zelio Time Relays - RE22R1ACMR
Relay Output

On and Off-delay Timing Relay - 0.05s…300h - 24…240V AC/DC - 1C/O

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Relay
    device short name
    RE22
    nominal output current
    8 A
    Complementary
    contacts type and composition
    1 C/O timed contact, cadmium free
    time delay type
    Ac
    Act
    time delay range
    0.05...1 s
    0.3...3 s
    1...10 s
    10...100 s
    3...30 h
    3...30 min
    3...30 s
    30...300 h
    30...300 min
    30...300 s
    control type
    Rotary knob
    Diagnostic button
    External potentiometer
    [Us] rated supply voltage
    24...240 V AC/DC at 50/60 Hz
    input voltage
    <= 2.4 V
    voltage range
    0.85...1.1 Us
    supply frequency
    50...60 Hz (+/- 5 %)
    connections - terminals
    Screw terminals : 1 x 0.5...1 x 3.3 mm², AWG 20...AWG 12 solid cable without cable end
    Screw terminals : 2 x 0.5...2 x 2.5 mm², AWG 20...AWG 14 solid cable without cable end
    Screw terminals : 1 x 0.2...1 x 2.5 mm², AWG 24...AWG 14 flexible cable with cable end
    Screw terminals : 2 x 0.2...2 x 1.5 mm², AWG 24...AWG 16 flexible cable with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % conforming to IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
    minimum pulse duration
    100 ms (with load in parallel)
    30 ms
    insulation resistance
    100 MOhm at 500 V DC conforming to IEC 60664-1
    reset time
    120 ms (on de-energisation)
    immunity to microbreaks
    <= 10 ms
    power consumption in VA
    3 VA at 240 V AC
    power consumption in W
    1.5 W at 240 V DC
    switching capacity in VA
    2000 VA
    minimum switching current
    10 mA 5 V DC
    maximum switching current
    8 A
    maximum switching voltage
    250 V AC
    electrical durability
    100000 cycles for 8 A at 250 V AC-1
    100000 cycles for 2 A at 24 V DC-1
    mechanical durability
    10000000 cycles
    [Uimp] rated impulse withstand voltage
    5 kV for 1.2...50 µs conforming to IEC 60664-1
    delay response
    < 100 ms
    creepage distance
    4 kV/3 conforming to IEC 60664-1
    overvoltage category
    III conforming to IEC 60664-1
    safety reliability data
    MTTFd = 205.4 years
    B10d = 190000
    mounting position
    Any position
    mounting support
    35 mm DIN rail conforming to EN/IEC 60715
    status LED
    Green LED backlight (steady) for dial pointer indication
    Yellow LED (steady) for output relay energised
    Yellow LED (fast flashing) for timing in progress and output relay de-energised
    Yellow LED (slow flashing) for timing in progress and output relay energised
    width
    22.5 mm
    product weight
    0.1 kg
    Environment
    dielectric strength
    2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation conforming to IEC 61812-1
    standards
    IEC 61812-1
    UL 508
    directives
    2004/108/EC - electromagnetic compatibility
    2006/95/EC - low voltage directive
    product certifications
    CCC
    CE
    CSA
    GL
    UL
    RCM
    EAC
    China RoHS
    ambient air temperature for operation
    -20...60 °C
    ambient air temperature for storage
    -40...70 °C
    IP degree of protection
    IP20 (terminals) conforming to IEC 60529
    IP40 (housing) conforming to IEC 60529
    IP50 (front face) conforming to IEC 60529
    pollution degree
    3 conforming to IEC 60664-1
    vibration resistance
    20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
    shock resistance
    15 gn (not operating) (duration = 11 ms) conforming to IEC 60068-2-27
    5 gn (in operation) (duration = 11 ms) conforming to IEC 60068-2-27
    relative humidity
    95 % at 25...55 °C
    electromagnetic compatibility
    Fast transients immunity test (test level: 1 kV, level 3 - capacitive connecting clip) conforming to IEC 61000-4-4
    Surge immunity test (test level: 1 kV, level 3 - differential mode) conforming to IEC 61000-4-5
    Surge immunity test (test level: 2 kV, level 3 - common mode) conforming to IEC 61000-4-5
    Electrostatic discharge (test level: 6 kV, level 3 - contact discharge) conforming to IEC 61000-4-2
    Electrostatic discharge (test level: 8 kV, level 3 - air discharge) conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test (test level: 10 V/m, level 3 - 80 MHz...1 GHz) conforming to IEC 61000-4-3
    Conducted RF disturbances (test level: 10 V, level 3 - 0.15...80 MHz) conforming to IEC 61000-4-6
    Fast transient bursts (test level: 2 kV, level 3 - direct contact) conforming to IEC 61000-4-4
    Immunity to microbreaks and voltage drops (test level: 30 % - 500 ms) conforming to IEC 61000-4-11
    Immunity to microbreaks and voltage drops (test level: 100 % - 20 ms) conforming to IEC 61000-4-11
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
  • Documents and Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Date 4/30/18
    Size 7.7 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 8/6/18
    Size 1.5 MB
    UL Listed RE17, RE22, REXL, RE48A, RE88857, RE88865, RE88867, RENF22R2MMW
    Instruction sheet
    Date
    Size
    Add to My Documents
    Date 2/2/18
    Size 805.6 KB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 8/6/18
    Size 243.3 KB
    End of life manual
    Date
    Size
    Add to My Documents
    Product environmental
    Date
    Size
    Add to My Documents
    REACh Declaration
    Date
    Size
    Add to My Documents
    RoHs Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Connections and Schema

    Wiring Diagram



  • Technical Description

    Function Ac: On-Delay & Off-Delay with Control Signal
    Description

    After energisation of power supply and energization of Y1 causes the timing period T to start.

    At the end of this timing period, the output(s) R close(s).

    When deenergization of Y1, the timing T starts.

    At the end of this timing period T,the output(s) R revert(s) to its/their initial position.

    The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").

    Function: 1 Output


    Function: 2 Outputs



    Function Act: On-Delay & Off-Delay with Control Signal & With Pause / Summation Control
    Description

    After energisation of power supply and energization of Y1 causes the timing period T to start and the timing can be interrupted / paused each time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R close(s).When deenergization of Y1, the timing T starts and the timing can be interrupted / paused each time X1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial position.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").

    Function: 1 Output


    T =
    t1 + t2 +…
    T =
    t'1 + t'2 +…

    Function: 2 Outputs


    T =
    t1 + t2 +…
    T =
    t'1 + t'2 +…

    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    U -

    Supply

    T -

    Timing period

    R1/R2 -

    2 timed outputs

    R2 inst. -

    The second output is instantaneous if the right position is selected

    X1 -

    Pause / Summation control

    Y1 -

    Retrigger / Restart control