Zelio Time Relays - RE17RLMU

Relay Output

RE17RLMU Product picture Schneider Electric
View all Zelio Time Relays
Zelio Time Relays - RE17RLMU
Relay Output

asymmetrical flashing relay - 1 s..100 h - 24..240 V AC - 1 OC

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Relay
    width
    17.5 mm
    device short name
    RE17R
    time delay type
    L
    Li
    time delay range
    0.1...1 s
    1...10 h
    1...10 min
    1...10 s
    10...100 h
    6...60 min
    6...60 s
    nominal output current
    8 A
    Complementary
    contacts type and composition
    1 C/O
    contacts material
    Cadmium free
    control type
    Selector switch on front panel
    [Us] rated supply voltage
    24...240 V AC at 50/60 Hz
    24 V DC
    voltage range
    0.85...1.1 Us
    supply frequency
    50...60 Hz (+/- 5 %)
    input voltage
    10 V
    connections - terminals
    Screw terminals, clamping capacity: 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12 (solid) without cable end
    Screw terminals, clamping capacity: 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14 (solid) without cable end
    Screw terminals, clamping capacity: 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14 (flexible) with cable end
    Screw terminals, clamping capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16 (flexible) with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % conforming to IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
    impulse duration
    100 ms with load in parallel typical
    30 ms typical
    insulation resistance
    100 MOhm at 500 V DC conforming to IEC 60664-1
    reset time
    120 ms on de-energisation typical
    on-load factor
    100 %
    power consumption in VA
    0...32 VA at 240 V AC
    power consumption in W
    <= 0.6 W at 24 V DC
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    8 A AC/DC
    maximum switching voltage
    250 V AC
    breaking capacity
    <= 2000 VA
    operating rate in Hz
    10 Hz
    electrical durability
    100000 cycles for resistive load (8 A at 250 V AC maximum)
    mechanical durability
    10000000 cycles
    dielectric strength
    2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
    [Uimp] rated impulse withstand voltage
    5 kV (1.2/50 µs)
    delay response
    < 100 ms
    marking
    CE
    creepage distance
    4 kV/3 conforming to IEC 60664-1
    safety reliability data
    MTTFd = 296.8 years
    B10d = 270000
    mounting position
    Any position in relation to normal vertical mounting plane
    mounting support
    35 mm DIN rail conforming to EN/IEC 60715
    local signalling
    LED indicator on steady: relay energised, no timing in progress
    LED indicator flashing: timing in progress (80 % ON and 20 % OFF)
    product weight
    0.07 kg
    Environment
    immunity to microbreaks
    <= 20 ms
    standards
    2004/108/EC
    EN 61000-6-1
    EN 61000-6-2
    EN 61000-6-3
    EN 61000-6-4
    IEC 61812-1
    2006/95/EC
    product certifications
    CSA
    cULus
    GL
    ambient air temperature for storage
    -30...60 °C
    ambient air temperature for operation
    -20...60 °C
    IP degree of protection
    IP20 (terminal block) conforming to IEC 60529
    IP40 (housing) conforming to IEC 60529
    IP50 (front panel) conforming to IEC 60529
    vibration resistance
    20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
    shock resistance
    15 gn (duration = 11 ms) conforming to IEC 60068-2-27
    relative humidity
    93 % without condensation conforming to IEC 60068-2-30
    electromagnetic compatibility
    Electrostatic discharge immunity test, in contact at 6 kV conforming to IEC 61000-4-2 level 3
    Electrostatic discharge immunity test, in air at 8 kV conforming to IEC 61000-4-2 level 3
    Susceptibility to electromagnetic fields, 80 MHz to 1 GHz at 10 V/m conforming to IEC 61000-4-3 level 3
    Electrical fast transient/burst immunity test, capacitive connecting clip at 1 kV conforming to IEC 61000-4-4 level 3
    Electrical fast transient/burst immunity test, direct at 2 kV conforming to IEC 61000-4-4 level 3
    1.2/50 µs shock waves immunity test, differential mode at 1 kV conforming to IEC 61000-4-5 level 3
    1.2/50 µs shock waves immunity test, common mode at 2 kV conforming to IEC 61000-4-5 level 3
    Conducted RF disturbances, 0.15...80 MHz at 10 V conforming to IEC 61000-4-6 level 3
    Voltage dips and interruptions immunity test, 1 cycle at 0 % conforming to IEC 61000-4-11
    Voltage dips and interruptions immunity test, 25/30 cycles at 70 % conforming to IEC 61000-4-11
    Conducted and radiated emissions conforming to EN 55022 class B
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Available
  • Documents and Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Date 4/30/18
    Size 7.7 MB
    Certificate
    Date
    Size
    Add to My Documents
    UL Listed RE17, RE22, REXL, RE48A, RE88857, RE88865, RE88867, RENF22R2MMW
    Date 10/23/18
    Size 1.9 MB
    Instruction sheet
    Date
    Size
    Add to My Documents
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 8/6/18
    Size 242.8 KB
    End of life manual
    Date
    Size
    Add to My Documents
    Date 12/13/17
    Size 1.4 MB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Width 17.5 mm



  • Connections and Schema

    Internal Wiring Diagram



    Wiring Diagram


    1
    Link A1-Y1 for function L only


  • Technical Description

    Function L : Asymmetrical Flasher Relay (Starting Pulse Off)
    Description

    Repetitive cycle comprises of two, independently adjustable timing periods Ta and Tr. Each timing period corresponds to a different state of the output R.

    Function: 1 Output



    Function Li : Asymmetrical Flasher Relay (Starting Pulse On)
    Description

    Repetitive cycle comprises of two, independently adjustable timing periods Ta and Tr. Each timing period corresponds to a different state of the output R.

    Function: 1 Output



    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    C

    Control contact

    G

    Gate

    R

    Relay or solid state output

    R1/R2

    2 timed outputs

    R2 inst.

    The second output is instantaneous if the right position is selected

    T

    Timing period

    Ta -

    Adjustable On-delay

    Tr -

    Adjustable Off-delay

    U