2 Ethernet ports interface 100BASE-FX, ACE850FO for Sepam series 40, 60, 80

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Sepam series 40
    Sepam series 80
    Sepam series 80 NPP
    Sepam series 60
    device short name
    ACE850FO
    optic fiber type
    Multi mode wavelength: 1300 nm connector(s): SC
    Complementary
    communication port protocol
    ARP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    FTP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    HTTP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    IEC 61850 network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    Modbus RTU network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    Modbus TCP/IP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    RSTP 801.1d 2004 network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    SNMP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    SNTP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
    local signalling
    Green LED1 for energized on front face
    Green LED2 for communication status ok on front face
    Green LED3 for port 2 Ethernet 100 Mbit/s on front face
    Green LED4 flashing for port 2 Ethernet sending data and receiving data on front face
    Green LED5 for port 1 Ethernet 100 Mbit/s on front face
    Green LED6 flashing for port 1 Ethernet sending data and receiving data on front face
    Red LED1 flashing for not set up or not base-unit connected on front face
    Red LED1 off for de-energized on front face
    Red LED1 remains ON for fault on front face
    [Us] rated supply voltage
    110...240 V AC tolerance: - 20...10 %
    24...250 V DC tolerance: - 20...10 %
    mounting mode
    Fixed
    mounting support
    Symmetrical DIN rail
    height
    127 mm
    width
    171 mm
    depth
    58 mm
    product weight
    0.4 kg
    mechanical robustness
    Earthquakes in operation ( level: 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3
    Earthquakes in operation ( level: 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3
    Jolts de-energized ( level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
    Shocks de-energized ( level: 2) : 30 Gn/11 ms conforming to IEC 60255-21-2
    Shocks in operation ( level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
    Vibrations de-energized ( level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
    Vibrations in operation ( level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
    Vibrations in operation ( level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6
    optic fiber length
    2000 m diameter: 50/125 µm optical power (dBm) -14
    2000 m diameter: 62.5/125 µm optical power (dBm) -14
    auxiliary connection terminal
    Functional earth : ring lug 1 pin(s) 1 cable(s) 4 mm²
    Protective earth : screw-type connector 1 pin(s) 1 cable(s) wire 2.5 mm² <= 3 m
    Supply : screw-type connector 2 pin(s) 1 cable(s) wire 0.2...2.5 mm²
    Supply : screw-type connector 2 pin(s) 1 cable(s) wire 1.5 mm²
    Supply : screw-type connector 2 pin(s) 1 cable(s) wire 2.5 mm²
    Supply : screw-type connector 2 pin(s) 2 cable(s) wire 0.2...1 mm²
    Supply : screw-type connector 2 pin(s) 2 cable(s) wire 1 mm²
    wire stripping length
    Supply : 8 mm
    Environment
    electromagnetic compatibility
    1 MHz damped oscillating wave immunity tests-conducted disturbances : III (2.5 kV MC, 1 kV MD ) conforming to IEC 60255-22-1
    Fast transient bursts immunity tests-conducted disturbances : A or B (4kV, 2.5 kHz/2 kV, 5 kHz ) conforming to IEC 60255-22-4
    Fast transient bursts immunity tests-conducted disturbances : IV (4kV, 2.5 kHz ) conforming to IEC 61000-4-4
    Immunity to magnetic fields at network frequency immunity tests-radiated disturbances : IV (30 A/m (continuous)-300 A/m (13 s) ) conforming to IEC 61000-4-8
    Immunity to radiated fields immunity tests-radiated disturbances : III (10 V/m, 80 MHz...2 GHz ) conforming to IEC 61000-4-3
    Surges immunity tests-conducted disturbances : III (2 kV MC, 1 kV MD ) conforming to IEC 61000-4-5
    Conducted disturbance emission emission tests : B conforming to EN 55022
    Disturbing field emission emission tests : A conforming to EN 55022
    1 MHz damped oscillating wave immunity tests-conducted disturbances (2.5 kV MC and MD ) conforming to ANSI C37.90.1
    100 kHz damped oscillating wave immunity tests-conducted disturbances (2.5 kV MC, 1 kV MD ) conforming to IEC 61000-4-12
    Conducted disturbance emission emission tests conforming to IEC 60255-25
    Disturbing field emission emission tests conforming to IEC 60255-25
    Electrostatic discharge immunity tests-radiated disturbances (8 kV air, 4 kV contact ) conforming to ANSI C37.90.3
    Electrostatic discharge immunity tests-radiated disturbances (8 kV air, 6 kV contact ) conforming to IEC 60255-22-2
    Fast transient bursts immunity tests-conducted disturbances (4kV, 2.5 kHz ) conforming to ANSI C37.90.1
    Immunity to conducted RF disturbances immunity tests-conducted disturbances (10 V ) conforming to IEC 60255-22-6
    Immunity to radiated fields immunity tests-radiated disturbances (10 V/m, 80 MHz...1 GHz ) conforming to IEC 60255-22-3
    Immunity to radiated fields immunity tests-radiated disturbances (35 V/m, 25 MHz...1 GHz ) conforming to ANSI C37.90.2 (1995)
    Voltage interruptions immunity tests-conducted disturbances (100 %, 10 ms ) conforming to IEC 60255-11
    climatic withstand
    Continuous exposure to damp heat (in operation) : Ca : 10 days, 93 % RH, 40 °C (104 °F) conforming to IEC 60068-2-3
    Continuous exposure to damp heat (in storage) : Ca : 56 days, 93 % RH, 40 °C (104 °F) conforming to IEC 60068-2-3
    Exposure to cold (in operation) : Ab : - 25 °C (- 13 °F) conforming to IEC 60068-2-1
    Exposure to cold (in storage) : Ab : - 25 °C (- 13 °F) conforming to IEC 60068-2-1
    Exposure to dry heat (in operation) : Bb : 70 °C (158 °F) conforming to IEC 60068-2-2
    Exposure to dry heat (in storage) : Bb : 70 °C (158 °F) conforming to IEC 60068-2-2
    Influence of corrosion/gaz test 2 (in operation) : C : 21 days, 75 % RH, 25 °C (- 13 °F), 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60
    Temperature variation with specified variation rate (in operation) : Nb : - 25 °C to 70 °C (- 13 °F to 158 °F) 5 °C/min (41 °F/min) conforming to IEC 60068-2-14
    Salt mist (in operation) : Kb/2 conforming to IEC 60068-2-52
    Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm S02, 0.02 ppm NO2, 0.01 ppm Cl2 conforming to IEC 60068-2-60
    ambient air temperature for operation
    -25...70 °C
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
  • Documents and Downloads

    Language
    • English
    • French
    Catalogue
    Date
    Size
    Add to My Documents
    Catalogue Sepam serie 20, 40, 60, 80 - Cover (Version 6.0)
    User guide
    Date
    Size
    Add to My Documents
    Sepam series 40, user's manual (Version 10)
    Date 12/21/17
    Size 10.7 MB
    CAD
    Date
    Size
    Add to My Documents
    ACE850 types CAD (Version 1.0)
    Date 8/17/12
    Size 817.6 KB
    Instruction sheet
    Date
    Size
    Add to My Documents
    ACE850, Sepam multi-protocol communication interfaces (Version 01)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.