What are the Contact Resistance values for the Evolis 24KV Circuit Breaker.

The contact resistance values for the Evolis 24KV Circuit Breaker are tabulated below :


 

Evolis 24KV

16kA -630A

25kA-1250A

31.5kA-2500A

Fixed

Withdrawable

Fixed

Withdrawable

Fixed

Withdrawable

Contact Resistance

current supplied : I = 100 A

< 55 µΩ < 80 µΩ < 45 µΩ < 70 µΩ < 30 µΩ < 35 µΩ